If you plan to use a regulated power supply you may encounter a problem with regeneration. If you rapidly decelerate a
load from a high speed, much of the kinetic energy of that load is transferred back to the power supply. is can trip the
over-voltage protection of a switching power supply, causing it to shut down. We oer the RC-050 “regeneration clamp”
to solve this problem. If in doubt, buy an RC-050 for your rst installation. If the “regen” LED on the RC-050 never ashes,
you don’t need the clamp.
RC-050 Regen Clamp
+5V Keep-Alive Feature:
+5Volts can be fed to the +5V terminal to keep the logic alive when the DC bus voltage is removed. is is very useful
when an encoder is present, as the position of the system is then known when the DC bus is re-applied. An internal volt-
age fault will have to be cleared and the motor re-enabled when the DC bus is re-applied. A .4 Amp or larger supply is
required for the keep-alive supply.
12
SWM24 Hardware Manual
920-0068B
10/31/2013